DATA CENTERS + ENERGY
Switchgear
OSENSA’s FTX-910/610/310-PWR+R fiber optic temperature transmitters provide continuous real-time temperature monitoring of switchgear, busbars, and other medium voltage electrical equipment rated up to 38kV. Each transmitter accepts from three to nine optical fiber sensor inputs. The FTX-910/610/310-PWR+ transmitters are powered by 12~24VDC and include isolated RS485 serial connectivity over industry standard Modbus RTU protocol. Multiple transmitters can be connected in series on a standard 35mm DIN rail with power and RS-485 communication supplied by the five-pin T-Bus connector. Also included are two programmable 2A relays for over-temperature alarms. The HTX-100-PWR is a battery powered handheld device typiclaly used during installation and troubleshooting.