PD_PDX800.png

8 Ch, RS-485, PD Reader

OSENSA’s PDX-800 monitors up to eight PDA-100 ultra-high frequency (UHF) smart sensors. It utilizes high-speed digital signal processing to detect energy bursts from partial discharge events in medium and low voltage applications such as switchgear, bus ducts, and dry-type transformers. The device phase synchronizes to 50Hz or 60Hz line frequencies and can output high resolution phase resolved cloud plots. Primary sensor data includes ambient temperature, ambient humidity, maximum PD, and total PD. The synchronized AC waveform data indicates peak line-earth and line-line PD levels allowing for phase resolved troubleshooting.


Product Specs

Number Of Channels
8
Operating Environment
-40°C to +75°C
Communication Protocol
Modbus RTU, Half Duplex
Power
12-24 VDC (2.5W max)
Alarms
Max PD, Total PD, Temp, Humidity
UHF Sensitivity
5o pC to 1 μC (equivalent)
Update Rate
1.25 seconds per channel
Operating Humidity
0 to 90% RH (Non-Condensing)
Dimensions
102mm Tall x 45mm Wide x 114mm Long
Mounting
35mm DIN Rail
Ambient Temperature
Reported per channel
Ambient Humidity
Reported per channel

Compatible Products

Partial Discharge Solutions
Switchgear, Dry Type Transformer

Ultra-high frequency (UHF) temperature & humidity PD Sensor.

Number Of Channels:
1
Operating Environment:
-40°C to +75°C
Communication Protocol:
Proprietary
Partial Discharge Solutions
Switchgear, Dry Type Transformer

Partial discharge simulator.